| Power-Donut2™
Specifications |
|
|
Diameter: |
12.5 inches (32 cm) 5.5 inches
(14 cm) Corona free
housing through 500 kV, Fully Weatherproof |
![]() |
|
| Power
Supply Battery Power: |
No external
power supply is required, the Power-Donut™ is powered from the magnetic
field, and internal lithium battery pack. Nominal low current required
to operate -- 50 Amps.
|
|
Measures
Demand/Vars:
Inclination: |
Conductor current, Voltage (phase to ground), 2 conductor temperatures, conductor inclination angle. +/- 0.5% of reading, (Voltage and current scale verified on site) Measures demand, reactive demand, I-V phase angle, demand hours and reactive demand hours +/- 1 deg C accuracy, 0.1 deg C resolution +/- 0.05 degrees accuracy, 0.01 degree resolution |
|
Monitors Warning & Alarms:
|
Measurements and computed values Three user definable warning and alarm levels on all analog inputs and monitor points Computes sag and tension based on conductor inclination, user input conductor specifications Stores users selected measurements and computed values in Flash RAM. Logging intervals are user selectable Monitors internal unit temperatures, battery parameters, power supply voltages |
|
Communication Cell Phone:
|
Power-Donut2™ communicates using patented TDMA polling methodology. GSM Cell
Phone 850 MHz / 900 MHz |
| Software | USi real-time data acquisition and control software is available. The software operates with Microsoft Windows 2000 and Windows XP operating systems on Pentium class processors. |
| Options | Weather station is available for use with DLR and UPRATE™ applications |
|
USi
84 Business Park Drive, Suite 109 Armonk, New York 10504 |
|